Split Range Control

 

A very common control scheme is split range control in which the output of a controller is split to two or more control valves. For example:

 

 

Different arrangements are possible. For example, figure 1 shows a split range pressure controller on a separator with two valves, one to the flare and one to the compressor suction. In this case, the ‘split’ is configured as follows:

 

 

The idea is that the suction valve is used for normal pressure control while the flare valve only opens to disperse high pressures.

 

Figure 1. Split range control scheme

 

In this application, the flare valve will need to open quickly in response to high pressures, but the compressor suction valve will need to move much more slowly to prevent instability in the compressors. The main problem with split range control is that the controller only has one set of tuning parameters. If the controller is tuned to be fast acting to optimise the performance of the flare valve, the suction valve will also move rapidly to produce unstable gas flows to the compressors. If the controller is tuned slower to stabilise the compressors, then the flare valve will not open fast enough as the pressure rises. A further issue is that the process response of the route to flare generally differs to the process response of the route to the compressors, so both routes will anyway require very different tuning for optimal control.

 

The solution is to replace the split range controller with two independent controllers, both reading the same pressure transmitter, but one controlling the flare valve and the other the suction valve. Not only can each controller be tuned correctly for its dedicated service, but different setpoints can also be used to prevent the flare valve from ‘popping’ unnecessarily.

 

Figure 2. Correct implementation

 

The ease with which a split range controller can be replaced with two ordinary controllers depends on a number of factors. If the ‘split’ is calculated in the DCS or PLC so that each valve has its own output from the control system, then the addition of a new controller is simply a matter of software configuration. However, occasionally, the control system only has one output wired to both controllers and the ‘split’ produced by configuration of the valve positioner. A new output will then be required from the control system to one of the valves and the valve positioners must be reconfigured to operate over the full 0-100% output range.

 